DALI
A DALI‑2 master in the gateway: commission, name, dim, group and scene every luminaire.
Connect
Wire the DALI line to the DALI terminal (polarity does not matter). A DALI bus needs its own power supply: the gateway does not power the bus, so install a DALI PSU on the line. Install DALI‑2 from Integrations; the status shows Built‑in DALI · 1 line and whether the bus has power.
Find your lights
- + Add device finds every luminaire that already has a short address and lists it, ready to add.
- Commission new addresses unaddressed gear (a new installation, or a driver you just added) and assigns free short addresses (0–63).
- Add a light manually if you already know its short address.
Each light gets a name and a room and shows up in Rooms right away. Open one to dim, set colour temperature on tunable‑white drivers (Warmer, relaxed / Cooler, brighter feel), reassign its address, put it in a group (0–15), save a scene, or read energy and diagnostics.
Groups and scenes
Groups let one command move many luminaires at once; scenes store a level per light. Both are saved in the drivers themselves, so keypads on the same line keep working with them.
Sharing the bus
The gateway can be Master (control) or Observer (listen‑only) when another control system already runs the line. Observer mode reads everything without interfering. The Setup panel tells you if it sees another master or collisions, and reminds you never to add a second power supply.
Push‑buttons and sensors
DALI‑2 input devices (buttons, occupancy, light sensors) send events that appear as triggers in Workflows.
Self‑healing
If the bus receiver looks unhealthy the page shows Degraded — self‑healing; the gateway recovers on its own and counts the recoveries so you can spot a wiring problem.